Engineering Resources • Checklist

Instrumentation Loop Check Checklist

Merobix Engineering •

A checklist for instrument technicians and commissioning engineers proving loops end to end: field device, wiring and marshalling, controller I/O, and the HMI. Use it one loop at a time, on screen or printed - checkbox state is not saved between visits. It reflects common practice; your site’s procedures and sign-off forms govern.

Back to Resources

Step 1 - Before You Start

Step 2 - Field Device

Step 3 - Wiring and Marshalling

Step 4 - Controller I/O: the 5-Point Check

Inject at the field device terminals (preferred, because it proves the wiring) or at marshalling if the device end is inaccessible, and read the result in the controller.

PointSignal on a 4-20 mA loopVerify in the controller
0%4.0 mARaw counts and scaled engineering value at range low
25%8.0 mAScaled value at 25% of range
50%12.0 mAScaled value at midscale
75%16.0 mAScaled value at 75% of range
100%20.0 mARaw counts and scaled engineering value at range high

Step 5 - HMI and Historian

Step 6 - Alarm Limit Checks

Step 7 - Fail-Direction Verification

Prove what the loop does when it is broken - before the process proves it for you.

Step 8 - Documentation