Automation Glossary • Mount a DP Transmitter Below the Tap

How to Mount a DP Transmitter Below the Tap

Merobix Engineering • • 7 min read

For liquid service, the rule of thumb is to mount a DP transmitter below the process tap so the impulse lines fill and stay full of liquid, and to slope them so any gas rises back to the process rather than collecting at the cell. Mount it wrong, above the tap or with a flat run, and gas pockets or drained legs corrupt the differential in ways that look like a drifting measurement. This guide walks mounting a DP transmitter below the tap for liquid, covering the slope, the self-filling principle, and the mounting-head suppression it creates.

Back to Blog

Mount a DP Transmitter Below the Tap in one line: To mount a DP transmitter below the tap for liquid service, place the transmitter below the process connections and run the impulse lines continuously downward to it with a steady slope, so the lines self-fill with liquid and any gas bubbles rise back to the process. This keeps the reference legs solid and the reading stable. The transmitter sees the head of the filled impulse legs even at zero process differential, so you suppress that mounting head when you set the range.

Understand Why Below-Tap Mounting Works for Liquid

In liquid service the impulse lines must stay full of liquid to transmit pressure faithfully, and gravity is your ally if you use it. Mounting the transmitter below the taps means the lines run downhill from process to cell, so liquid naturally fills them and stays there, and any gas that comes out of solution rises back up the line to the process and vents itself rather than lodging at the transmitter. A solid, gas-free liquid leg is what gives a stable, correct differential.

The opposite, mounting above the taps or running lines with a rise, invites trouble because gas collects at the high point next to the cell and drained legs lose their liquid. For gas or vapour service the logic inverts, transmitter above so condensate drains back, but for the common liquid-level and liquid-flow case, below-tap with a downward slope is the standard. This is the installation side of the differential-pressure transmitter, and it determines whether the clean electronics ever see a clean pressure.

Slope the Impulse Lines Continuously

Run each impulse line with a continuous downward slope from the tap to the transmitter, with no flat sections and no local high or low points where gas or dirt can collect. A consistent grade lets gas migrate up to the process and any sediment settle toward a drain rather than into the cell. Both legs should be routed alike, side by side where possible, so they share the same temperature and behave symmetrically, since a difference between the two legs shows up directly in the differential.

Keep the runs as short and as equal as practical, and provide isolation valves and a manifold at the transmitter so you can equalize and zero it. The impulse lines are the weak link in any DP measurement, and their condition is what a leak check of impulse lines confirms and a routine blowdown clears. A well-sloped, self-draining pair of legs is the difference between a DP loop that holds its zero for years and one that wanders every time a bubble forms.

Account for the Mounting-Head Suppression

Mounting below the tap has a consequence you must handle in the configuration: the filled impulse legs put a static head on the transmitter even when the real process differential is zero. On a single filled leg or an unbalanced arrangement, that mounting head is a fixed offset the transmitter reads at zero process condition, and you suppress it so the 4 mA point corresponds to the true zero condition, not to the leg head. This is the same suppression concept that appears whenever a transmitter sits below its measuring point.

The clean way to capture and remove it is to zero the transmitter in place, with the process at a known condition and the legs filled, so the mounting head is measured and trimmed out. On a balanced wet-wet arrangement the two leg heads largely cancel, but any imbalance remains and is captured in the zero. The mechanics of doing this with the manifold are the 3-valve manifold blowdown and zero procedure, done after the legs are filled and stable.

Verify the Installation

Confirm the legs are truly full and gas-free before trusting the reading. After filling, equalize the manifold and check that the transmitter reads a stable zero differential; a wandering or non-zero equalized reading points to a gas pocket or an unequal fill in one leg. Vent the high points if the design provides vents, or bleed at the transmitter, until the equalized zero is solid. A stable equalized zero is the direct proof that both legs are behaving.

Then verify the measurement against reality, a hand dip for level or a check meter for flow, at operating conditions. When the loop feeds a monitoring history, an impulse-line problem from a poorly sloped or draining leg has a recognizable signature: a slow drift or a stepwise shift in the reading that correlates with temperature cycles or process events as gas forms and clears. Seeing the reading wander with conditions rather than with the real process points back at the impulse legs and the mounting.

Avoid the Common Mistakes

The mounting mistakes are running impulse lines with a flat section or a rise that traps gas next to the cell, mounting above the taps for liquid so the legs can drain, and letting the two legs differ in routing or temperature so an imbalance appears in the differential. Forgetting to suppress the mounting head leaves a fixed offset, and zeroing the transmitter before the legs are properly filled bakes a gas-pocket error into the zero.

Because a leg problem produces a reading that drifts and steps rather than failing outright, it is easily mistaken for a drifting sensor, sending people to recalibrate electronics that are fine. Trending the DP reading against temperature and process events in a monitoring platform reveals a leg fault by its correlation with conditions rather than with the real variable. The history points at the legs; an equalized-zero check and a look at the slope confirm whether gas or a drained leg is the cause.

Frequently Asked Questions

Why mount a DP transmitter below the tap for liquid service?

So the impulse lines self-fill with liquid and stay full. With the transmitter below the taps, the lines run downhill and gravity keeps them full of liquid, while any gas that forms rises back up to the process and vents itself instead of lodging at the cell. A solid, gas-free liquid leg is what gives a stable, correct differential. For gas or vapour service the logic inverts and the transmitter goes above the tap so condensate drains back, but liquid service wants below-tap mounting.

How should impulse lines be sloped?

Continuously downward from the tap to the transmitter, with no flat sections and no local high or low points where gas or dirt can collect. A steady grade lets gas migrate up to the process and sediment settle toward a drain rather than into the cell. Route both legs alike, side by side where possible, so they share temperature and behave symmetrically, because any difference between the two legs shows up directly in the differential the transmitter reports.

What is mounting-head suppression on a below-tap DP transmitter?

It is removing the fixed static head that the filled impulse legs put on the transmitter even when the real process differential is zero. Because the transmitter sits below the taps, the liquid-filled legs press on it at zero process condition, so you suppress that offset when setting the range and capture it by zeroing the transmitter in place with the legs filled. On a balanced wet-wet arrangement the leg heads largely cancel, but any imbalance is captured in the in-place zero.

More in Instrumentation & Measurement
Magnetostrictive level operation  •  Calibrate a Displacer Level Transmitter  •  Calibrate a Square-Root Flow Transmitter  •  Calibrate a Temperature Transmitter  •  Calibrate a Transmitter at Line Pressure  •  All Instrumentation & Measurement →
Free SCADA operator training
Merobix University - 70 video lessons & 261 quiz questions, from first login to compliance reporting. No demo call required.
Start free →