Automation Glossary • Forward_Open Request

What Is a Forward_Open Request in CIP?

Merobix Engineering • • 5 min read

Every EtherNet/IP I/O connection and every connected explicit message starts with one request: Forward_Open. It is where the connection points, sizes, timing, and keying are all negotiated in a single exchange, and where most connection failures are actually decided. This page explains what a Forward_Open request is, what it carries, and why its response codes are the first thing to read when a connection will not establish.

Back to Blog

Forward_Open Request in one line: A Forward_Open is the CIP service, handled by the Connection Manager object, that establishes a connection. It carries the connection points (assembly instances), the data sizes, the RPI, the connection type, and the electronic-keying data. The target validates all of it and either accepts, opening the connection, or refuses with a status code that names exactly what did not match.

What a Forward_Open Negotiates

A Forward_Open is a single request that bundles everything a connection needs to be agreed. It names the connection points - the assembly instances the originator wants to consume from and produce to - and the sizes in bytes of each. It specifies the RPI for each direction, which sets both the update rate and the connection timeout. It states the connection type, so the target knows whether this is cyclic I/O or connected explicit messaging. And it carries the electronic-keying fields - vendor, product code, revision - that the target checks against its own identity.

The target validates all of this at once. If the assembly instance does not exist, the size does not match, the RPI is unsupportable, or the keying does not satisfy the configured level, the target refuses. Because so much is agreed in one request, the Forward_Open response is where most connection problems are decided, and its status code points directly at the failing element rather than leaving you to guess. The service is handled by the Connection Manager object, which owns connection setup and teardown.

A successful Forward_Open leaves an established connection with reserved resources at both ends and a defined timeout. From that point the data flows - cyclically for an I/O connection, on request for a Class 3 explicit connection - without renegotiation. The connection persists until it is closed with a Forward_Close or until it times out from silence.

Reading a Forward_Open Failure

Because the Forward_Open carries so many parameters, its failure response is diagnostic gold. A keying error means the vendor, product code, or revision in the request did not satisfy the device's identity and keying level - a wrong module or a firmware mismatch. A size or connection-point error means the assembly instance or its byte count was wrong - the wrong assembly was selected, or its size was miscounted. A resource error means the device cannot accept another connection of that type, often because its connection pool is exhausted.

Interpreting these codes is the core skill of diagnosing EtherNet/IP connectivity, and the general framework is in reading a CIP general status code. The value of the Forward_Open is that it fails early and specifically: rather than a vague no-comms symptom, you get a status that says whether the problem is identity, sizing, timing, or resources. Reading that status is far faster than swapping cables and rebooting hoping the symptom moves.

Forward_Open in the Connection Lifecycle

The Forward_Open opens the connection; its counterpart Forward_Close cleanly tears it down, releasing the reserved resources at both ends. A connection can also end without a Forward_Close if it simply stops being served and times out, which is what happens when a device is powered off or a cable is pulled - the surviving end sees the timeout and faults the connection. Understanding this lifecycle explains why some faults clear on a clean reconnect and others leave a device holding a stale connection until its timeout expires.

For the wider system, the Forward_Open is entirely a field-side and controller-side affair; SCADA does not issue it. A monitoring platform such as Merobix reads the controller's tags after the controller's connections are up. When a device shows as faulted or its data goes stale, the root cause is frequently a Forward_Open that is now being refused - a swapped module failing keying, a changed assembly failing on size - and diagnosing at that level is what restores the tags the SCADA layer depends on.

Frequently Asked Questions

What does a Forward_Open request do?

It establishes a CIP connection in one exchange. The originator sends the connection points (assembly instances), data sizes, RPI, connection type, and electronic-keying fields; the target validates all of them and either opens the connection or refuses with a status code naming what failed. It is handled by the Connection Manager object and precedes both I/O and connected explicit messaging.

Why did my Forward_Open fail?

The response status names the reason. A keying error means the vendor, product code, or revision did not match the device and its keying level. A size or connection-point error means the assembly instance or its byte count was wrong. A resource error means the device cannot accept another connection of that type. Reading the Forward_Open status is far faster than blindly swapping cables.

What is the difference between Forward_Open and Forward_Close?

Forward_Open establishes a connection, negotiating its points, sizes, RPI, type, and keying and reserving resources at both ends. Forward_Close cleanly tears that connection down and releases the resources. A connection can also end without a Forward_Close by timing out from silence, which is what happens when a device is powered off or unplugged rather than closed gracefully.

More in General Automation Concepts
Commission a store-and-forward repeater  •  Configure Store-and-Forward Buffering  •  Configure store-and-forward on a cellular gateway  •  Monitor a CIP System  •  Read a CIP Status Code  •  All General Automation Concepts →
Free SCADA operator training
Merobix University - 70 video lessons & 261 quiz questions, from first login to compliance reporting. No demo call required.
Start free →