Automation Glossary • Water-Side Economizer

What Is a Water-Side Economizer?

Merobix Engineering • • 7 min read

When the weather is cold and damp enough, a cooling tower can make water cold enough to cool a building without ever starting a chiller - the tower and a heat exchanger do the work the compressor normally does. That is the water-side economizer, a free-cooling strategy that lives in the chiller plant rather than at the air handler. This guide describes how a water-side economizer uses condenser water and a plate-and-frame heat exchanger to produce chilled water, the difference between integrated and non-integrated modes, the changeover setpoints, and the approach-temperature limits - framed for data-center and large-plant operators tracking efficiency in a cloud historian.

Back to Blog

Water-Side Economizer in one line: A water-side economizer produces chilled water without running the chiller by using cold condenser water from the cooling tower and a plate-and-frame heat exchanger to cool the chilled-water loop directly. It works when the outdoor wet-bulb temperature is low enough for the tower to make condenser water colder than the required chilled water, plus a heat-exchanger approach. In integrated mode it can also pre-cool the return water ahead of a running chiller when the wet-bulb is only partly favorable.

How the Tower and Heat Exchanger Replace the Chiller

In normal operation a chiller sits between two water loops: it absorbs heat from the chilled-water loop that serves the building and rejects it into the condenser-water loop that runs to the cooling tower. A water-side economizer bypasses the chiller's compressor by connecting those loops through a plate-and-frame heat exchanger instead. When the cooling tower can produce condenser water colder than the chilled water the building needs, that cold tower water flows through one side of the heat exchanger and cools the building's chilled-water loop on the other side, so the tower and heat exchanger together do the job the chiller usually does.

The cooling tower's ability to make cold water is set by the outdoor wet-bulb temperature, not the dry-bulb, because a tower cools by evaporation. On a cold, dry night the wet-bulb can be low enough that the tower produces condenser water well below the chilled-water setpoint, leaving room for the heat exchanger to transfer the load. The compressor - the largest energy consumer in the plant - stays off, and cooling is delivered for the cost of running pumps and tower fans, which is a fraction of the chiller's power.

The plate-and-frame heat exchanger is central because it keeps the two loops physically separate while allowing efficient heat transfer through thin metal plates. Its performance is described by an approach temperature - the gap between the two loops' temperatures it can achieve - and that approach directly determines how cold the wet-bulb must be before free cooling becomes possible. A tighter approach lets the economizer work in more hours of the year, which is why heat-exchanger selection matters to the economizer's total value.

Integrated vs Non-Integrated Modes and Changeover

A non-integrated water-side economizer is an all-or-nothing arrangement: either the tower and heat exchanger carry the entire load with the chiller off, or the chiller runs and the economizer is out of the picture. It is simpler to pipe and control, but it captures free cooling only during the hours when the wet-bulb is cold enough for the tower alone to meet the full load, and it wastes the many partial hours when the tower could carry some but not all of the cooling.

An integrated water-side economizer captures those partial hours by putting the heat exchanger in series ahead of the chiller. When the wet-bulb is only partly favorable, the economizer pre-cools the return chilled water as far as the tower can, and the chiller then does the remaining, smaller amount of cooling to reach setpoint. Because the chiller only has to make up the difference, it runs at a much lighter load and lower energy, so the plant gains free cooling across a far wider range of conditions than a non-integrated design. In data centers, where cooling load is high and constant year-round, integrated economizing is the norm because it harvests every hour of favorable weather.

Changeover between modes is governed by comparing the wet-bulb, or the achievable condenser-water temperature, against the chilled-water setpoint plus the heat-exchanger approach. The plant enters full economizer mode when the tower can make chilled water on its own, integrated mode when it can help but not fully, and mechanical cooling when the wet-bulb is too high. Getting these changeover setpoints right - with enough deadband to avoid rapidly cycling between modes - is what makes the economizer capture its potential without hunting.

Approach Limits and Tracking Efficiency in the Cloud

The whole strategy is bounded by approach temperatures. The cooling tower has a tower approach - how close its condenser water can get to the ambient wet-bulb - and the heat exchanger has its own approach between the condenser and chilled-water loops. Stacking these approaches determines the minimum wet-bulb at which free cooling becomes possible: the colder and drier the weather relative to the chilled-water setpoint plus both approaches, the more hours the economizer runs. Fouled tower fill or a fouled heat exchanger widens these approaches and quietly shrinks the free-cooling window, which is a degradation that does not announce itself.

Because the value of a water-side economizer is measured in energy avoided rather than in comfort, it is exactly the kind of asset that benefits from trended data. Operators want to see condenser-water supply temperature against wet-bulb, the heat exchanger's actual approach, and whether the plant is in economizer, integrated, or mechanical mode at any given time - and to compare that against how many free-cooling hours the weather should have allowed. A gap between available and captured free-cooling hours points to a changeover misconfiguration or a fouled component.

This is a headline use case for pushing plant data to a cloud historian. A platform such as Merobix can collect condenser-water and chilled-water temperatures, wet-bulb, tower fan and pump status, and mode transitions from the plant controllers and trend them centrally, so a data-center or large-plant operator can verify the economizer is capturing the free cooling the climate offers and catch a widening approach before it costs a season of savings. For an operator responsible for chiller-plant efficiency, that continuous, remote view of the water-side economizer's performance is what turns a designed capability into realized energy savings.

Frequently Asked Questions

How is a water-side economizer different from an air-side economizer?

An air-side economizer brings cool outdoor air directly into the air handler to cool the building, modulating dampers in the mixing box. A water-side economizer keeps the air handlers drawing chilled water but makes that chilled water without a chiller, using cold cooling-tower condenser water and a plate-and-frame heat exchanger. Air-side works at the air handler and depends on dry-bulb or enthalpy; water-side works in the chiller plant and depends on the wet-bulb.

What is the difference between integrated and non-integrated water-side economizing?

A non-integrated economizer is all-or-nothing: the tower and heat exchanger either carry the full load with the chiller off, or the chiller runs and the economizer is idle. An integrated economizer puts the heat exchanger in series ahead of the chiller, so during partly favorable weather it pre-cools the return water as far as the tower allows and the chiller makes up only the remainder. Integrated designs capture far more free-cooling hours, which is why data centers favor them.

Why does a water-side economizer depend on wet-bulb temperature?

Because a cooling tower cools by evaporation, its lowest achievable water temperature is set by the outdoor wet-bulb, not the dry-bulb. When the wet-bulb is low enough that the tower can produce condenser water colder than the required chilled water - plus the heat-exchanger and tower approaches - free cooling becomes possible. On a cold, dry night the wet-bulb can be low enough for the tower and heat exchanger to carry the load with the chiller off.

From Definitions to a Live Dashboard

Merobix reads your field devices into a cloud SCADA - the real thing behind these terms, live in days from any browser.

Request a Free Demo +1 (903) 307-7300
More in Automation Glossary
Chiller Plant Optimization  •  Chilled Water Reset  •  Condenser Water Reset  •  Booster Pump Station  •  Pressure Zone  •  District Metered Area  •  All Automation Glossary →
Free SCADA operator training
Merobix University - 70 video lessons & 261 quiz questions, from first login to compliance reporting. No demo call required.
Start free →