IEC 61850 Buffered vs Unbuffered Reporting
IEC 61850 offers two report control block types, and choosing wrong means either lost events or wasted buffer memory. This page compares buffered and unbuffered reporting - how each behaves during a client disconnect, what each costs, and which data belongs on which - so you can configure a client for reliable sequence-of-events without over-engineering.
Buffered vs Unbuffered Reporting in one line: A buffered report control block (BRCB) queues events in the IED while a client is disconnected and delivers them with original timestamps on reconnect, so no event is lost. An unbuffered report control block (URCB) sends only current data and drops anything that occurred during the outage. Use buffered for events that must not be lost, unbuffered for live indication.
The Decision in One Paragraph
Choose by whether missing an event during a disconnect is acceptable. Protection operations, trips, alarms, and any sequence-of-events data must survive a client dropout, so they belong on a buffered report control block, which holds a queue of events in the IED and replays it - with the events' original timestamps - the moment the client reconnects. Live indication that is only meaningful right now, like a real-time status a wallboard shows, can use unbuffered reporting, which sends current values and simply forgets whatever happened while nobody was listening.
Buffering is not free: the IED holds a finite event queue, and a long enough disconnect can overflow it, after which the oldest events are lost and an overflow indication is set. So buffered reporting improves integrity but does not make it infinite - it buys time across normal reconnects, not indefinite storage.
Comparison and Configuration Notes
| Aspect | Buffered (BRCB) | Unbuffered (URCB) |
|---|---|---|
| During disconnect | Events queued in IED | Events dropped |
| On reconnect | Backlog delivered, original timestamps | Only current data |
| Best for | Trips, alarms, SOE | Live indication |
| Cost | Finite buffer, can overflow | Minimal state |
| Integrity | Sequence preserved across dropouts | Gaps on any dropout |
Both types are just modes of the report control block, so the dataset, trigger options, and optional fields are configured the same way; buffering is the added behavior. Reporting over MMS is the client-server path, distinct from the fast peer-to-peer GOOSE service. When events do not arrive after a reconnect, check whether the client reserved a BRCB rather than a URCB - a common cause of missing sequence-of-events data.
EntryID and Resynchronizing After a Dropout
The buffered report control block does more than queue events - it numbers them. Each buffered entry carries an EntryID and a time of entry, and the block maintains sequence numbering across reports. When a client reconnects, it can present the EntryID of the last report it processed, and the IED resumes delivery from the next entry onward, so the client receives exactly the missed portion of the backlog rather than a full replay. If the client's EntryID is no longer in the buffer - because the outage outlasted the queue - the device starts from the oldest entry it still holds, and the client should treat that as notice of a possible gap.
Two related mechanisms matter in practice. PurgeBuf lets a client deliberately clear the buffer, which is occasionally useful at commissioning but dangerous as a routine habit, since it discards exactly the history buffering exists to protect. And the buffer-overflow indication (BufOvfl) is the block's confession that events were lost; a client that ignores it will happily present an incomplete sequence-of-events record as if it were complete. A SCADA master's driver should surface both conditions, not swallow them.
Reservation and Serving More Than One Client
A report control block instance serves one client at a time. Buffered blocks support reservation, so a client can claim an instance and hold that claim across reconnects - which is what makes the resynchronization story work, since the buffer is being kept for that specific client. The consequence is an engineering rule: every client that needs its own event stream needs its own instance. A typical station allocates separate instances for the primary SCADA master, a backup master, and a local engineering client, each with the dataset it needs.
Instance shortages surface as mysterious integration failures: the second master cannot enable reporting because the only instance is already reserved by the first. The number of instances is fixed in the device configuration, so count the clients early, during system design, and check the capability of each intelligent electronic device against that count per the manufacturer's documentation.
Keeping the Buffer for What It Is Good At
Buffer capacity is finite and device-specific, so what you put on a buffered block determines how much outage it can absorb. Discrete events - trips, alarms, status changes - are rare and small, and a buffer holds a long history of them. A chatty analog on a data-change trigger is the opposite: it generates entries continuously and can fill the buffer quickly, evicting the very trip records the block was supposed to protect. The sound pattern is to keep buffered blocks for event-class data, apply sensible deadbands to any analog that must be buffered, and let routine analog telemetry ride an unbuffered block or periodic integrity reports instead.
It is equally important to know what the buffer is not: it is transit protection, not storage. Once events are delivered, they leave the queue; the buffered block is not a historian and cannot be re-read later. Durable sequence-of-events archiving belongs in the station's event recorder or the upstream historian - the buffered block only guarantees the events survive the trip there. That division of labor is consistent with the rest of the IEC 61850 design, which separates real-time reporting services from long-term records.
A Commissioning Test Worth Running
Before a site is accepted, prove the buffering actually works end to end:
- Verify the dataset contents against the SCL engineering file, and confirm the configuration revision (ConfRev) the client expects matches what the device reports - a mismatch means the dataset changed after the client was configured.
- Reserve and enable the buffered block from the production client, then generate test events and confirm they arrive with correct timestamps.
- Disconnect the client - pull the cable or drop the tunnel - and generate more events while it is dark.
- Reconnect and verify the backlog arrives, in order, with the original event timestamps rather than the reconnection time.
- Confirm the client's handling of BufOvfl and of a purged buffer, so an overflow some future night produces an alarm rather than silent data loss.
Frequently Asked Questions
When should I use buffered reporting?
For any data where a missed event during a client disconnect is unacceptable - protection operations, trips, alarms, and sequence-of-events records. A buffered report control block queues those events and replays them with original timestamps on reconnect.
Can a buffered report control block still lose events?
Yes, if the disconnect lasts long enough to overflow the IED's finite event buffer. When that happens the oldest events are discarded and an overflow indication is set, so buffering extends integrity across normal reconnects rather than guaranteeing it forever.
Why did my client miss events after reconnecting?
A common cause is that the client enabled an unbuffered report control block, which drops anything that happened during the disconnect. Reserving and enabling a buffered report control block instead preserves the event backlog with original timestamps.
What does a ConfRev mismatch mean and why does it block reporting?
ConfRev is the configuration revision of the dataset behind the block; the device increments it when the dataset definition changes. A client comparing its expected ConfRev against the device's is detecting configuration drift - the events it would receive are no longer the ones its database was built for. The fix is to re-import the current engineering file into the client, not to ignore the mismatch, because index-based mapping against a changed dataset silently mislabels every point.
Are buffered reports a substitute for a sequence-of-events recorder?
No. The buffer protects events in transit across client disconnects; it is emptied as reports are delivered and can overflow during a long outage. Durable SOE records need an archive - the station historian, an event recorder, or both - fed by the buffered reports. Buffered reporting is what makes that archive complete despite communication dropouts, but the archive itself lives elsewhere.
Automation services
Need help turning this into a working system?
Merobix integrates SCADA, programs Allen-Bradley and Siemens PLCs, and designs and fabricates industrial control panels.
Meeting requests are reviewed before confirmation.