What Is EtherNet/IP?
EtherNet/IP is a widely used industrial Ethernet protocol built on the Common Industrial Protocol (CIP) and managed by ODVA. The name stands for EtherNet/Industrial Protocol - not internet protocol - and it is the native network of Rockwell Automation Allen-Bradley controllers, making it one of the most common protocols in North American plants.
EtherNet/IP in one line: EtherNet/IP is an industrial Ethernet protocol that runs the Common Industrial Protocol (CIP) over standard TCP/IP and UDP/IP, using explicit messaging for configuration and data reads and implicit (I/O) messaging for real-time cyclic control data.
CIP, Implicit and Explicit Messaging
EtherNet/IP adapts the Common Industrial Protocol to standard Ethernet. CIP is an object-oriented, media-independent application layer also used by DeviceNet and ControlNet, which means the same device profiles and object model carry across those networks. On EtherNet/IP, CIP messages travel two ways. Explicit messaging uses TCP for request/response transactions - reading a tag, changing a parameter, uploading configuration - where timing is not critical.
Implicit messaging (also called I/O messaging) uses UDP for real-time, cyclic data such as the produced/consumed I/O between a PLC and remote I/O racks or drives. UDP is used because its low overhead suits the repetitive, time-sensitive nature of control data, with connection setup and health monitoring handled by CIP. For deterministic motion, CIP Sync and CIP Motion add time synchronization on top.
EtherNet/IP in Oil and Gas SCADA
Because Allen-Bradley ControlLogix and CompactLogix processors use EtherNet/IP natively, it is extremely common on oil and gas skids, compressor packages, pump stations, and separator control panels across North America. A SCADA system typically reads controller tags over EtherNet/IP explicit messaging or through an OPC server that speaks the protocol.
For cloud SCADA, an edge gateway or driver reads the PLC's tags over EtherNet/IP locally and forwards a curated set upward over a routable, outbound connection. Merobix supports EtherNet/IP among its device protocols, so an operator running Allen-Bradley controllers can bring wellhead, compressor, or pump-station data into cloud dashboards, alarms, and a historian - polling the PLC locally and pushing data outbound, with no inbound ports opened on the site firewall.
Ports and Traffic Types on the Wire
EtherNet/IP uses a small, fixed set of well-known ports, which makes its traffic easy to recognize and easy to police:
| Traffic | Transport | Port | Purpose |
|---|---|---|---|
| Explicit messaging | TCP | 44818 | Tag reads, configuration, diagnostics |
| Encapsulation discovery | UDP | 44818 | List Identity and device discovery |
| Implicit I/O | UDP | 2222 | Cyclic produced and consumed control data |
The firewall rule that follows from the table: implicit I/O has no business crossing a zone boundary. Keep the cyclic UDP traffic inside the local control network where its timing is protected, and let only explicit, request-based reads leave - preferably originating outbound from an edge device rather than allowing anything inbound toward the controller. If a remote system needs controller data, the pattern described in connecting EtherNet/IP to cloud SCADA keeps the PLC polled locally with only an outbound connection leaving the site.
Multicast, Unicast, and the Switch Underneath
Implicit connections are established as multicast or unicast, and the choice decides what your switches must do. Multicast without IGMP snooping and a querier degenerates into flooding - every device on the segment receives every I/O packet, and small devices choke on traffic that was never meant for them. Modern practice prefers unicast connections where the devices offer the choice, and reserves multicast for topologies that genuinely need one producer feeding several consumers, running on managed switches configured for it.
When an I/O connection drops, the controller logs a connection fault and the I/O goes to its configured fault state, so treat the network as part of the machine: duplicate IP addresses, a flapping link, a saturated uplink, or an unmanaged switch quietly discarding bursts all present as intermittent connection loss. The walkthrough on diagnosing an EtherNet/IP I/O connection fault gives an ordered procedure; the short version is to establish whether the loss affects one device, one switch span, or the whole segment before touching any configuration.
Budgeting Connections and Update Rates
Every controller has a finite communications budget: a maximum number of CIP connections and a bounded number of packets per second it can service, both stated in the manufacturer's documentation for the specific processor and communication module. Each I/O connection consumes packet budget in proportion to how fast it cycles - its requested packet interval - so tightening every connection's update rate at once is how otherwise healthy systems run out of headroom. Plan the rates by need: machine-critical I/O fast, slowly changing skid data much slower, and verify the totals against the budget before commissioning rather than after the first mysterious connection timeout. Working through the arithmetic is covered in budgeting EtherNet/IP connections on a controller.
Polling Tags Without Hurting the Controller
Explicit reads from SCADA and historians land on the same communications budget, so poll design matters. Fewer, larger requests beat many small ones: group related tags into arrays or structures the driver can fetch in one transaction instead of scattering hundreds of individual tag reads. Split polling into rate classes - operator-facing values on a faster class, configuration and slowly moving values on a much slower one - and resist the reflex to poll everything at the fastest rate the driver allows. After any polling change, check the controller's reported communications load with the manufacturer's tools and confirm the control task scan has not stretched; the PLC's first duty is the machine, and a chatty SCADA driver should never compete with it.
Frequently Asked Questions
Does EtherNet/IP mean internet protocol?
No. The IP in EtherNet/IP stands for Industrial Protocol, referring to the Common Industrial Protocol (CIP) it carries. It does run over standard TCP/IP and UDP/IP Ethernet, but the name is about CIP, not the internet.
What is the difference between implicit and explicit messaging?
Explicit messaging uses TCP for on-demand request/response transactions like reading a tag or changing a parameter, where timing is flexible. Implicit (I/O) messaging uses UDP for real-time cyclic control data between controllers and I/O, where low, repeatable latency matters more than guaranteed delivery of every packet.
Which controllers use EtherNet/IP?
EtherNet/IP is the native protocol of Rockwell Automation Allen-Bradley controllers such as ControlLogix and CompactLogix, and it is supported by many drives, I/O, and instruments from ODVA member vendors. It is especially common in North American oil, gas, and manufacturing plants.
Is EtherNet/IP the same thing as Modbus TCP?
No - they are different protocols that happen to share Ethernet. EtherNet/IP carries the CIP object model, with named tags, device profiles, and both cyclic and request-based transfer. Modbus TCP exposes flat numbered registers with a much simpler read/write model. Many gateways and controllers speak both, and plants routinely run both side by side, but the drivers, addressing, and diagnostics are entirely different.
Do I need managed switches for EtherNet/IP?
For anything carrying implicit I/O, managed switches are the safe default: IGMP snooping for multicast, port diagnostics, and per-port error counters are what make faults findable. A tiny cell with a handful of unicast connections can survive on unmanaged hardware, but you give up visibility exactly where you will someday need it. Follow the controller vendor's network design guidance for the specific application.
Sources and verification
This page references the standards, specifications, and official documentation published by the organizations below. Editions, product capabilities, and documentation change over time - confirm current requirements and specifications directly with the source.
- Rockwell Automation Literature Library (Allen-Bradley, Studio 5000) - Rockwell Automation
- Modbus Application Protocol Specification - Modbus Organization
Merobix is not affiliated with, endorsed by, or sponsored by these organizations; their names are used only to identify the standards and products discussed.