How to Baseline a Pump-Off Controller Runtime
A pump-off controller does more than protect the pump; the pattern of how long it runs and how long it idles is one of the best low-cost indicators of what a rod-pumped well is doing. But a runtime number only means something against a baseline. This procedure establishes that baseline: a recorded picture of the well's normal run-and-idle behavior over stable days, so that later changes in runtime point to inflow decline, sanding, gas, or an equipment problem. It is a data-and-trending task, run after the controller's sensors and pump-off logic are verified and the well has settled.
Baseline POC Runtime in one line: To baseline a pump-off controller runtime, wait until the well and controller are stable, then record its daily runtime, idle time, and cycle count over several representative days, along with the pump-off setpoint and cards that were driving shutdowns. Capture the normal daily runtime percentage and the typical run-and-idle rhythm as the reference. Later, compare live runtime against this baseline: a falling runtime usually signals declining inflow, while a rising runtime or erratic cycling points to a pump or downhole problem.
Stabilize the Well and Settings First
A baseline is only useful if it captures normal behavior, so do not baseline a well that is still being tuned or is recovering from a workover. Confirm the pump-off logic is verified, the pump-off setpoint is set to a sensible value, and the well has run for enough cycles that its run-and-idle pattern has settled into a rhythm. If someone is still adjusting the setpoint or the pump-fillage threshold day to day, the runtime will move for those reasons and the baseline will be meaningless.
Record the settings that shape runtime so the baseline is interpretable later. Note the pump-off setpoint, the fillage or load threshold that triggers shutdown, the minimum idle time, and the pumping speed. Runtime is a function of these settings and the reservoir together, so a baseline without the settings recorded cannot be compared honestly to a future reading taken under different settings. Keeping the settings alongside the numbers is what makes the baseline durable.
Confirm the shutdowns during the baseline period are genuine pump-off events, not nuisance trips or faults. Look at the cards that triggered each shutdown and confirm they show real incomplete fill, and check that the controller is not idling on a bad signal or a spurious alarm. A baseline built on nuisance shutdowns records noise rather than the well, so clean up the trip cause before you trust the runtime pattern - the same discipline you would apply to any nuisance alarm.
Capture the Normal Run-and-Idle Pattern
With the well stable, record its behavior over several representative days, ideally covering a normal range of ambient and operating conditions. The core numbers are daily runtime, daily idle time, the runtime percentage of the day, and the number of pump-off cycles per day. Together these describe how hard the well is being pumped relative to what the reservoir can supply. A well running a modest fraction of the day is being cycled off frequently because inflow cannot keep the pump full; a well running most of the day is close to being inflow-limited.
Trend these values rather than storing a single day. A continuous record of runtime, captured by the monitoring system, shows the normal day-to-day scatter as well as the average, which is what you need to judge later whether a change is real or just normal variation. Storing the runtime as a trended tag alongside the well's other data lets you overlay it later against production and pressures. Treat runtime as a first-class monitored value, the same way you would treat any point you rely on for trending in SCADA.
Also record the cards and pressures that accompany the baseline runtime. The dynamometer cards during the baseline period establish what a normal shutdown looks like on this well, and the casing and tubing pressures at the time set the pressure context. When runtime later changes, having the baseline cards and pressures lets you tell whether the pump, the inflow, or the wellhead conditions moved. The runtime number is the headline; the cards and pressures are the supporting evidence.
Use the Baseline to Catch Changes
Once the baseline exists, the runtime becomes a diagnostic. A steady, gradual decline in daily runtime on an unchanged setup usually means the reservoir is supplying less liquid over time, so the pump fills more slowly and the controller idles it sooner and longer. This is the normal decline signature and it tells you the well may be a candidate for a speed reduction or a different lift strategy, not a repair. Reading it against the baseline is what distinguishes decline from a fault.
A sudden change points elsewhere. Runtime that drops abruptly, or cycling that becomes erratic and short, often means a mechanical or downhole problem: a sticking pump, a hole in tubing, sanding, or increasing gas. Compare the current cards and pressures against the baseline cards and pressures to localize it. An abrupt runtime change with normal-looking cards suggests a surface or controller issue; an abrupt change with degraded cards points downhole.
The checklist below captures the minimum you should record to make a runtime baseline useful. Store each item as trended data where you can, so the comparison later is a matter of overlaying live values on the baseline rather than hunting for old notes.
- Well is stable and pump-off logic verified before baselining.
- Pump-off setpoint, fillage threshold, minimum idle time, and speed recorded.
- Daily runtime, idle time, runtime percentage, and cycle count over several representative days.
- Representative dynamometer cards that triggered shutdowns during the period.
- Casing and tubing pressures during the baseline period.
- Confirmation that baseline shutdowns are genuine pump-off events, not nuisance trips.
Common Mistakes
The most common mistake is baselining an unsettled well, so the reference captures tuning noise rather than normal behavior. Wait until the run-and-idle rhythm has stabilized and the settings have stopped changing before you record the baseline.
The second is recording runtime without the settings that drive it, which makes any later comparison ambiguous because you cannot tell whether runtime moved due to the reservoir or a settings change. The third is treating a single day as a baseline; runtime varies day to day, and only a trend over several representative days captures the normal scatter you need to judge future changes against.
Frequently Asked Questions
What does a falling runtime on a pump-off controller mean?
On an unchanged setup, a steady decline in daily runtime usually means the reservoir is supplying less liquid, so the pump fills more slowly and the controller idles it sooner and longer. That is the normal decline signature and it may point to a speed reduction rather than a repair. A sudden or erratic drop, by contrast, points to a mechanical or downhole problem, which is why comparing against a recorded baseline matters.
How many days do I need to baseline runtime?
Enough days to capture the normal scatter and a representative range of operating conditions, not a single day. Runtime varies day to day with ambient temperature and small operational changes, so a several-day record shows both the average and the normal variation. Record daily runtime, idle time, runtime percentage, and cycle count across those days, and keep the controller settings alongside them so the baseline stays interpretable later.
Why record the settings with the runtime baseline?
Runtime is a function of both the reservoir and the controller settings, so a baseline runtime only means something paired with the setpoint, fillage threshold, minimum idle time, and speed that produced it. If someone later changes a setting, runtime will move for that reason, and without the recorded settings you cannot tell a settings change from a real well change. Store the settings with the numbers to keep the comparison honest.
Sources and verification
This page references the vendor products and their official documentation published by the organizations below. Editions, product capabilities, and documentation change over time - confirm current requirements and specifications directly with the source.
- Rockwell Automation Literature Library (Allen-Bradley, Studio 5000) - Rockwell Automation
- Siemens SIMATIC and TIA Portal documentation - Siemens
Merobix is not affiliated with, endorsed by, or sponsored by these organizations; their names are used only to identify the standards and products discussed.
Automation services
Need help turning this into a working system?
Merobix integrates SCADA, programs Allen-Bradley and Siemens PLCs, and designs and fabricates industrial control panels.
Meeting requests are reviewed before confirmation.