How to Verify a Pump-Off Controller Load Signal
A pump-off controller decides when to shut a rod-pumped well down using the load it reads from the polished rod, so a load signal that is off in zero, span, or direction leads directly to bad shutdowns and missed pump-off events. This procedure is the electrical and scaling verification you run after the load cell is mechanically installed and before you enable the controller's shutdown logic. It confirms the raw signal, the engineering-unit scaling, and that the reported load moves the right way through the stroke. It complements the mechanical install check and focuses on the number the controller acts on.
Verify POC Load Signal in one line: To verify a pump-off controller load signal, confirm the load cell reads a stable, plausible value at rest near the buoyant rod weight, check that the configured zero and span match the cell's calibration so engineering units are correct, and prove polarity by watching load rise on the upstroke. Then compare the controller's reported peak and minimum load against the pumping engineer's expected fluid load. A signal that is noisy, offset, or moving backward must be fixed before the controller is allowed to shut the well.
Check the Zero and the Resting Load
Start with the unit stopped near the bottom of the stroke and look at the raw and scaled load the controller reports. A correctly zeroed load cell reads close to the buoyant weight of the rod string at rest, a value the pumping engineer can estimate. If the reported load is far from that estimate, the zero is wrong or part of the load is bypassing the cell, and no amount of downstream logic will fix a bad zero. Record the resting value so you can confirm it holds after the well runs.
Confirm the reported load is stable, not drifting or jittering, while the unit is stopped. A resting load that wanders points to a loose connection, a cable working against the stuffing box, or electrical pickup on the signal pair. This is the cheapest place to catch noise, because a noisy load signal produces a fuzzy dynamometer card and erratic pump-off decisions once the unit runs. Fix instability at zero before you trust anything at speed.
If the controller uses a raw signal such as a 4-20 mA input from a load transducer, verify the loop electrically as well. Confirm the reading sits within the live 4-20 mA band rather than pegged at either end, since a signal stuck at saturation means an open or shorted loop rather than a real load. The same fault modes that appear on any analog input apply here, so treat it as an analog input loop check as much as a load verification.
Verify Span, Scaling, and Polarity
The zero sets the offset; the span sets how many pounds each unit of signal represents. Enter the cell's rated capacity and calibration factor exactly as the manufacturer's certificate gives them, because a span error scales every load reading proportionally and stretches or compresses the whole dynamometer card. If the controller supports a known-load check, apply or simulate a known load and confirm the reported value matches. Where a physical known load is not practical, at least confirm the configured span matches the cell's stamped rating.
Polarity is the check people skip and regret. Bar the unit over or run it slowly and watch the reported load: it must increase as the polished rod rises on the upstroke and decrease on the downstroke. A load signal wired backward produces an inverted card that reads as a pump fault, so the controller may shut a healthy well or fail to catch a real pump-off. Correct polarity in the wiring or the configuration and re-confirm before proceeding.
Cross-check the scaled load against the position so the two signals agree on where the stroke is. The peak load should coincide with the upstroke and the minimum with the downstroke. If peak load lands on the downstroke, either the load or the position direction is reversed. Getting load and position consistent is what lets the controller build a correct card and, in turn, a correct pump-off setpoint against which it decides to shut the well.
Confirm the Running Signal and Enable Protection
With zero, span, and polarity verified, run the well at normal speed and capture several cards. The peak load should approach the expected rod-plus-fluid load and the minimum should approach the buoyant rod weight, both consistent with the engineer's estimate. A load band that is shifted or compressed relative to those estimates means the scaling still needs work, even if the card shape looks fine. Verifying the absolute numbers here prevents a scaling error from later masquerading as a fluid-load change.
Confirm the load signal repeats stroke to stroke. Overlay consecutive cards and check the load level and shape are consistent; wandering load between strokes indicates an intermittent connection or noise that will corrupt pump-off detection. Only a stable, repeatable load signal is safe to base automatic shutdowns on. If the signal is stable, plausible in magnitude, and correctly directed, the load channel is verified.
Now the load signal is ready to feed the controller's logic, but do not enable automatic well shutdown on the strength of the load channel alone. The controller also needs a verified position signal to place each load in the stroke, so complete the position verification before arming pump-off protection. Enabling shutdown on a half-verified card risks the controller acting on a card that is scaled right but positioned wrong.
Common Mistakes
The most common mistake is trusting the card shape while ignoring the absolute load numbers. A card can look like a textbook full pump while every load value is wrong because the span was left at a default. Always compare the resting and peak loads against the engineer's estimates, not just the shape.
The second is skipping the polarity check because the card looks like a card. An inverted load signal produces a mirror-image card that reads as a pump problem, leading to nuisance shutdowns. The third is accepting a signal that is stable at rest but noisy at speed; noise only appears under vibration, so the running check matters as much as the resting one.
Frequently Asked Questions
What should the load read with the pumping unit stopped?
With the unit stopped near the bottom of the stroke, the reported load should sit close to the buoyant weight of the rod string, which the pumping engineer estimates from rod size, depth, and fluid level. A reading far below that suggests the zero is off or load is bypassing the cell; a reading far above suggests a zero or span error. Record this resting value so you can confirm the zero holds after the well runs.
How do I check that the load span is scaled correctly?
Enter the load cell's rated capacity and calibration factor from its certificate, then, if the controller supports it, apply or simulate a known load and confirm the reported value matches. Where a physical known load is impractical, confirm the configured span matches the cell's stamped rating and check that peak and minimum running loads land near the engineer's expected rod-plus-fluid and buoyant-weight values. A span error scales every reading and distorts the whole card.
Why does load polarity matter on a pump-off controller?
The controller assumes load rises on the upstroke to place each reading correctly on the card. If the load signal is wired backward, the card is inverted and a healthy well reads as a pump fault, so the controller may shut a good well or miss a real pump-off. Bar the unit over, confirm load increases as the polished rod rises, and correct the wiring or configuration before arming automatic shutdown.
Sources and verification
This page references the vendor products and their official documentation published by the organizations below. Editions, product capabilities, and documentation change over time - confirm current requirements and specifications directly with the source.
- Rockwell Automation Literature Library (Allen-Bradley, Studio 5000) - Rockwell Automation
- Siemens SIMATIC and TIA Portal documentation - Siemens
Merobix is not affiliated with, endorsed by, or sponsored by these organizations; their names are used only to identify the standards and products discussed.
Automation services
Need help turning this into a working system?
Merobix integrates SCADA, programs Allen-Bradley and Siemens PLCs, and designs and fabricates industrial control panels.
Meeting requests are reviewed before confirmation.