Automation Glossary • Winding Resistance Testing

What Is Motor Winding Resistance Testing?

Merobix Engineering • • 7 min read

Motor winding resistance testing measures the DC resistance of each phase of a motor's winding, down to the milliohm level, to find problems in the copper itself and its connections rather than in the insulation. A micro-ohmmeter or a dedicated winding-resistance tester passes a known current through the winding and measures the tiny voltage drop, from which it computes a resistance that should be very low and, importantly, closely matched across the three phases. Loose connections, corroded joints, broken conductor strands, and turn-to-turn shorts all show up as a resistance that is out of balance with the others, so the test is fundamentally about phase-to-phase comparison. This page explains how the measurement works, how phase balance and temperature correction are applied, and how it differs from insulation-resistance testing.

Back to Blog

Winding Resistance Testing in one line: Motor winding resistance testing measures the DC resistance of each phase winding at the milliohm level using a micro-ohmmeter, to detect loose or corroded connections, broken strands, and turn-to-turn shorts. The three phase resistances should be closely balanced, typically within a small percentage of each other, so the test is judged mostly on phase-to-phase balance, with readings corrected to a common reference temperature for comparison. It measures the health of the copper and its joints, unlike insulation-resistance testing, which measures the winding-to-ground insulation.

How the Milliohm Measurement Works

A motor winding is made of copper with a very low resistance, so measuring it meaningfully requires an instrument built for small values. A micro-ohmmeter, sometimes called a low-resistance ohmmeter or a ductor, passes a known, relatively large DC current through the winding and measures the small voltage that current produces across it, then applies Ohm's law to report the resistance. To avoid the resistance of the test leads and contacts corrupting such a small reading, the instrument uses a four-terminal, or Kelvin, connection, injecting current through one pair of leads and sensing voltage through a separate pair, so only the winding's own resistance is measured.

The reading is taken across each phase in turn, giving three values that, on a healthy motor, should be very low and closely matched to one another. Because the copper's resistance changes with temperature, the current is kept flowing only briefly and the winding is allowed to settle so its temperature is stable and known, since self-heating during the test would skew the reading. On some windings with significant inductance the measurement needs a moment for the current to stabilize before a valid reading is captured, which good instruments handle automatically.

The absolute resistance value is compared against the expected value for that motor design where such data exists, but the more powerful comparison is among the three phases. Because all three phases of a symmetric motor should have essentially the same winding resistance, any meaningful difference between them points to a problem in the phase that reads differently, regardless of whether a design reference is available. This is why winding resistance testing is fundamentally a balance test: the phases check each other.

Phase Balance, Temperature Correction, and What Imbalance Reveals

The acceptance criterion for winding resistance is usually expressed as a maximum allowable spread between the phases, typically within a small percentage of each other, with the exact figure taken from the motor manufacturer's data or the applicable standard. A set of three closely matched readings indicates sound windings and connections; a reading that is noticeably higher or lower than the other two singles out that phase as having a problem. A phase reading high suggests a loose or corroded connection, a poor termination, or broken conductor strands that reduce the effective copper carrying the current, all of which add resistance. A phase reading low can point toward shorted turns, where some of the winding is bypassed, reducing its resistance.

Temperature correction is essential because copper's resistance rises appreciably with temperature, so a reading taken warm differs from one taken cold, and readings compared across time or between machines are only meaningful at a common reference. The practice is to record the winding temperature at the time of the test and correct the measured resistance to a standard reference temperature, commonly twenty-five degrees Celsius, using the known temperature coefficient of copper. Without this correction, a temperature difference between two tests could masquerade as a change in the winding, or hide a real one, so the correction is not optional for trending.

Comparing corrected phase resistances across periodic tests turns a spot check into a trend. A phase whose corrected resistance has been matched to the others and is now creeping up over successive tests is showing a connection that is gradually loosening or corroding, or strands that are progressively failing, well before the joint overheats or the phase opens. Because a high-resistance joint runs hot under load and can cascade into a burned termination or single-phasing, catching a rising phase resistance early is a genuinely valuable predictive signal, and the balance framing makes the change easy to spot against the two healthy phases.

How It Differs From Insulation Testing and Fits Field Maintenance

Winding resistance testing and insulation-resistance testing are complementary and measure entirely different things, which is a common source of confusion. Insulation-resistance testing, and its polarization-index and dielectric-absorption variants, measure the winding-to-ground insulation, applying a high DC voltage and looking for tiny leakage currents through the insulation, so they find moisture, contamination, and insulation aging. Winding resistance testing measures the resistance of the copper conductor itself and its joints, passing current through the winding at low voltage, so it finds loose connections, broken strands, and shorted turns. One asks whether the insulation is keeping the current where it belongs; the other asks whether the copper and its connections are sound.

A complete off-line motor test regimen typically includes both, because a motor can pass one and fail the other. A winding with perfect insulation resistance can still have a loose terminal connection that a resistance test catches, and a winding with balanced, healthy resistance can still have degraded insulation heading for a ground fault that only the insulation test catches. Running the two together, along with tests like the surge comparison for turn-to-turn insulation, builds a picture no single test provides, which is why they appear together in motor maintenance and acceptance procedures.

Winding resistance testing is an off-line test done with the motor de-energized, so it is not a live cloud SCADA measurement, but its results belong in the same asset-condition record as the online data the running motor produces. A platform like Merobix that keeps periodic winding-resistance results alongside the motor's on-line current balance, temperature, and load history lets a maintainer connect a phase imbalance found at the last outage with the phase-current imbalance or hot connection the motor has been showing in service. For a fleet of motors across remote and unmanned sites, holding these off-line results centrally lets maintenance prioritize which machines to attend to, using a rising or imbalanced phase resistance as an early, physical warning of a connection or winding problem that on-line current data may only hint at.

Frequently Asked Questions

What does an imbalance between phase winding resistances indicate?

A phase that reads noticeably higher than the other two usually indicates added resistance from a loose or corroded connection, a poor termination, or broken conductor strands. A phase that reads noticeably lower can point toward shorted turns, where part of the winding is bypassed. Because the three phases of a healthy motor should be closely matched, any meaningful spread singles out the problem phase, which is why the test is judged mostly on phase-to-phase balance.

Why is temperature correction needed for winding resistance tests?

Copper's resistance rises appreciably with temperature, so a reading taken warm differs from one taken cold. To compare readings across time or between machines, the winding temperature is recorded at the time of the test and the measured resistance is corrected to a standard reference, commonly twenty-five degrees Celsius, using copper's known temperature coefficient. Without this correction a temperature difference could look like a change in the winding, or mask a real one, making trended comparisons unreliable.

How is winding resistance testing different from insulation resistance testing?

Winding resistance testing measures the DC resistance of the copper conductor and its joints at low voltage, finding loose connections, broken strands, and shorted turns. Insulation resistance testing applies a high DC voltage and measures tiny leakage currents through the winding-to-ground insulation, finding moisture, contamination, and insulation aging. One checks whether the copper and connections are sound; the other checks whether the insulation is intact. A complete motor test uses both because a motor can pass one and fail the other.

From Definitions to a Live Dashboard

Merobix reads your field devices into a cloud SCADA - the real thing behind these terms, live in days from any browser.

Request a Free Demo +1 (903) 307-7300
More in Automation Glossary
Surge Comparison Test  •  Overload Trip Class  •  Full-Load Amps (FLA)  •  Volts-per-Hertz (V/f) Control  •  Sensorless Vector Control  •  VFD Flying Start  •  All Automation Glossary →
Free SCADA operator training
Merobix University - 70 video lessons & 261 quiz questions, from first login to compliance reporting. No demo call required.
Start free →